Fuel Consumption
Gallons per Hour (GPH) .84 1.68 3.6
BTUH
Input/Output (x100) 125/100 240/200 450/382
Dimensions
Height (with burner on F450) 24" 36" 40" / 54"
Width (with burner on F200) 24" 38" 40"
Length (with blower & burner on F125) 84" 37" 55" / 79"
Stack
Inches of Diameter 6" 8" 8"
Height (without elbows) 10' 12' 14'
Draft (inches of water) -0.03 to -.04 -0.03 to -.04 -0.03 to -.04
Compressed Air Requirements
SCFM (maximum) 2 2 2
PSIG 30 30 30
Air Connection
Fitting Size to Air Regulator 1/4 NPT 1/4 NPT 1/4 NPT
Flame
Length - Changes with Oil Pressure (Avg) 2' 3-1/2' 4'
Diameter - Approximate 10" 12" 18"
Air Tube
Diameter - Enters into combustion chamber 4" 4" 5"
Length - Inside of combustion chamber 1-5/8" 1-5/8" 4-1/2"
Opening - Into combustion chamber of furnace 4-1/4" 4-1/4" 5-1/4"
Convenience Controls
Additional attempts to establish flame Yes
Automatic nozzle clean-out Yes
Hour Meter Yes
Dirty filter indicator Yes
Switch to test spark ignition Yes
Cabinet Construction
Material Gauge, Aluminum 12 14 14
Weight (pounds) 350 450 850
Furnace Air Movement via Prop or Squirrel Cage Blower
Blower Motor (HP)* 1/3 1/2 1-1/2
Capacity - CFM (max) 1,000 2,400 4,000
Motor Speed (RPM) 1,100 1,100 1,725
Outlet Openings 6" 25" 36" x 35"
Static Pressure - blower unit only (in. - H20) n/a n/a .25 - .4
Electrical
Total current draw (in amps) - maximum 17
Volts 120 120 240
Required circuit protection (in amps) 20
Frequency - Hz 60
Thermostat Voltage 120
Ignition Transformer, 23 ma secondary, continuous duty shielded transformer 10,000V
Intermittent spark ignition (10 seconds) Yes
Burner Motor
Horsepower 1/5
RPM 3,450
Fuel Pump
Suntec Model A2RA Waste Oil Pump Yes
Oil Nozzle
Delavan Aspirated Nozzle #30609-3.1 #30609-3.1 #30609-5
Equipment Provided
Vapor elimination from oil Yes
Filtration after oil heating Yes
Heater Switch Included
Line voltage thermostat Included
Barometric Damper Included
Floating oil pickup assembly Included
Check Valve Included
Return flow vent system Included
Installation & Maintenance Manual Included
Warranty - One yr full warranty on parts (not labor), 10 yr limited on furnace cabinet
* The F200 with squirrel cage blower has 1 horsepower motor